INSTALLING OPTIONS

View and Download Eaton 9355 installation manual online. Powerware Series Tie Cabinet For use with Eaton 9355 20/30 kVA UPSs. 9355 UPS pdf manual download. Eaton 5P Installation User Manual. 3-Apr-2013 4566 kB. Eaton 5PX - Eaton 5PX UPS firmware Upgrade Instructions. 22-Feb-2016 1359 kB. Eaton 5PXUPS EBM Manual. Eaton 9155 and 9355 (10/15 kVA) Internal Battery Instructions. English (US) 31-Jul-2015 189 kB. Powerware 9355 8 – 15 kVA User’s Guide. View and Download Eaton 9355 installation manual online. Powerware Series Tie Cabinet For use with Eaton 9355 20/30 kVA UPSs. 9355 UPS pdf manual download.

EATON Powerware

®

9355 Tie Cabinet (20/30 kVA) Installation Guide

S 164201630 Rev A www.powerware.com

22

8.

Route the wiring through the conduit from the communication wiring access
plate to the opening between the two X-Slot communication bays on each UPS
(see Figure 16).

Figure 16. Routing the Cables

9.

Install the CAN Bridge Card wiring between each UPS (see Figure 18 on
page 25).

Use three wires of the four-wire twisted-pair wire. (Reserve two wires for
pull-chain wiring in Step 11.) Be sure to check correct polarity for Pins 8 and 9:

S

Connect SHIELD Pin 10 on all cards together.

S

Connect CAN H Pin 9 and CAN L Pin 8 (twisted pair) on all cards together.

Advertising
Popular Brands
Popular manuals
Advertising

EATON Powerware

®

9355 Tie Cabinet (20/30 kVA) Installation Guide

S 164201630 Rev A www.powerware.com

19

Chapter 4

Eaton 9355 Ups Service Manual

Installing Options

This section describes the Powerware Hot Sync CAN Bridge Card.

For other options, such as additional X-Slot

t

cards, Powerware LanSafe

®

Power

Management Software, remote emergency power-off (REPO), relay output contacts,
or programmable signal inputs, refer to the Powerware 9355 UPS (20/30 kVA)
Installation and Operation Manual
.

Figure 12 shows the location of the communication options and control terminals on
the UPS.

DB-9 Communication Port

REPO (normally open)

Signal Input 2

Signal Input 1

X-Slot
Communication
Bay #2

X-Slot

Manual

Communication

Bay #1

Relay Output Contacts

Control

Terminals

Eaton 9355 Ups User Manual

REPO (normally closed)

Pull-Chain Output
Contacts (parallel only)

Eaton 9355 User Manual

Figure 12. Communication Options and Control Terminals

Powerware Hot Sync CAN Bridge Card

The Powerware Hot Sync CAN Bridge Card, shown in Figure 13, can be installed to
provide connectivity for operational mode control and metering of a parallel system at
any UPS in the system.

Plug-in Terminal Block

Eaton 9355 Installation Manual

Figure 13. Powerware Hot Sync CAN Bridge Card